Home » Shop » hot sale » Absolute Process Instruments API 4310 G _ DC to DC transmitter, low-level input. Fully isolated.

Absolute Process Instruments API 4310 G _ DC to DC transmitter, low-level input. Fully isolated.

Original price was: $287.20.Current price is: $155.11.

Sale!

66 in stock

SKU: API 4310 G Category:

Absolute Process Instruments API 4310 G _ DC to DC transmitter, low-level input. Fully isolated.

Features:

  • Factory Set Custom I/O Ranges
  • Easy-to-Install Plug-In Design
  • Full 2000 V Input/Output/Power Isolation
  • Input and Output LoopTracker® LEDs
  • Output Test Button
  • Built-In Loop Power Supplies for Input and Output

Applications:

  • Convert, Boost, Rescale Process Signals
  • Isolate Single-Ended (Common Ground) PLC Inputs
  • Interface Signals with Panel Meters, PLCs, Recorders, Data Acquisition, DCS, and SCADA Systems

The API 4310 G are factory configured to accept a DC voltage or current input and provide an optically isolated DC voltage or current output that is linearly related to the input.

The API 4310 G utilizes an ultra-stable input amplifier for reliable operation with input signals as low as 10 mVDC.

Typical applications include signal isolation, conversion, boosting or a combination of the three. Full 3-way isolation (input, output, power) makes this module useful for ground loop elimination, common mode signal rejection or noise pickup reduction.

When a milliamp input is specified, a loop excitation power supply is included that may be wired for sinking or sourcing to allow you to use a powered or passive input device.

When a milliamp output is ordered, it provides power to the output current loop (sourcing).

Common ranges as well as custom ranges are possible.

LoopTracker

API exclusive features include two LoopTracker LEDs (green for input, red for output) that vary in intensity with changes in the process input and output signals. These provide a quick visual picture of your process loop at all times and can greatly aid in saving time during initial startup and/or troubleshooting.

Output Test

An API exclusive feature includes the Functional Test Button to provide a fixed output (independent of the input) when held depressed. The test output level is factory set via an internal potentiometer to approximately 50% of output span. The functional test button greatly aids in saving time during initial startup and/or troubleshooting.

Installation

The API 4310 G plug into an industry standard 8-Pin octal socket sold separately. Sockets API 008 and fingersafe API 008 FS allow either DIN rail or panel mounting. The plug-in design, 3-way isolation, and robust electronics allows the module to be quickly hot-swapped without removing the power or I/O signals.

Specifications Table:

DC Input Range
  • Voltage: 0-10 mVDC to 0-100 mVDC
  • Bipolar voltage: ±10 mVDC to ±100 mVDC
  • Current: 0-100 µADC to 0-1 mADC
Input Impedance (Voltage) 200 kΩ minimum
Input Voltage Burden (Current) 1.25 VDC maximum
Common Mode Rejection 120 dB minimum
Input Loop Power Supply 18 VDC nom., unregulated, 25 mADC, max. ripple, <1.5 Vp-p (May be selectively wired for sinking or sourcing mA input)
DC Output Range Factory configured, specify output range

  • Voltage, 10 mA max.: 0-1 VDC to 0-10 VDC
  • Bipolar voltage: ±1 VDC to ±10 VDC
  • Current: 0-1 mADC to 0-20 mADC, 20 V compliance, 1000 Ω at 20 mA
Output Calibration Multi-turn zero & span potentiometers, ±15% span adj. typ.
Output Loop Power Supply 20 VDC nominal, regulated, 25 mADC, max. ripple <10 mVRMS
Output Test Sets output to test level when pressed. Test level factory set to approx. 50% of span. Specify custom setting.
Output Ripple and Noise Less than 10 mVRMS
Linearity Better than ±0.1% of span
Response Time 70 milliseconds typical
Ambient Temperature Range and Stability
  • “10°C to +60°C operating ambient
  • Better than ±0.04% of span per °C stability, calculated, not tested
Response Time 300 milliseconds typical
Isolation
  • 2000 VRMS minimum
  • Full isolation: power to input, power to output, input to output
Installation Environment
  • IP 40, requires installation in panel or enclosure
  • Use with API 008 or API 008 FS socket
  • Socket mounts to 35 mm DIN rail or can be surface mounted UL 508C pollution degree 2 environments or better
Power 115 VAC ±10%, 50/60 Hz, 2.5 W max