Home » Shop » hot sale » Absolute Process Instruments APD 44L3 D _ Specify VDC or mADC range

Absolute Process Instruments APD 44L3 D _ Specify VDC or mADC range

Original price was: $341.40.Current price is: $178.02.

Sale!

11 in stock

SKU: APD 44L3 D Category:

Absolute Process Instruments APD 44L3 D _ Specify VDC or mADC range

Cecomp Electronics, APD 44L3 D, DC to DC Signal Conditioner Low Select Function from 3 Inputs, 9-30VDC/10-32VAC Power

Features:

  • Versions to Follow the Highest or the Lowest Input
  • 1200 V Input/Output/Power Isolation
  • Input LoopTracker® LED
  • Zero and Span Output Calibration Potentiometers
  • Functional Test Button
  • Built-In Loop Power Supply for Output

Applications:

  • Track Highest or Lowest of Multiple Input Signals
  • Monitor Maximum Flow From Multiple Pumps
  • Sensor Redundancy

The APD 44L3 D accepts 3 voltage or current inputs, depending on the model. They provide an optically isolated DC voltage or current output that is linearly related to the highest or lowest of the inputs, depending on the model.

They are used where the highest or lowest of multiple inputs are required to drive the output, or where sensor redundancy is needed. Full 3-way isolation (input, output, power) makes this module useful for ground loop elimination, common mode signal rejection or noise pickup reduction. The inputs are not isolated from each other.

The APD 44L3 D Transmittor can be wired to allow a mA output to be either sinking (passive) or sourcing (active).

LoopTracker

API exclusive features include a green LoopTracker LED that varies in intensity with changes in the process input signal. It provides a quick indication of your process input at all times and can greatly aid in saving time during initial startup and/or troubleshooting.

Functional Test

An API exclusive feature includes the Functional Test Button to provide a fixed output (independent of the input) when enabled. The test output level is potentiometer adjustable from 0 to 100% of output span. The functional test button greatly aids in saving time during initial startup and/or troubleshooting.

Specifications Table:

Input 0-50 mV to 0-10 VDC, ±25mV to ±10VDC, 0-1 mA to 0-20 mADC, ±0.5 to ±20 mA

Factory Configured: Low select from 3 inputs. Specify 3 input ranges.

Output 0-1 V to ±10 VDC or 0-2 mA to 0-20 mA, 4-20 mA. Specify VDC or mADC range.
DC Input Range Factory configured, please specify each input range. Consult factory for special ranges and/or functions. Each input can have different ranges and/or units. Specify order of math functions if required. Milliamp inputs are sinking.

  • Voltage: 0-50 mVDC to 0-10 VDC
  • Bipolar voltage: ±25 mVDC to ±10 VDC
  • Current: 0-1 mADC to 0-20 mADC
  • Bipolar current: ±0.5 mADC to ±20 mADC
Input Impedance
  • Voltage: 50 kΩ minimum
  • Current: 50 Ω nominal
Balance Between Inputs Better than ±0.5% of span
DC Output Range Factory configured, please specify output range

  • Voltage, 10 mA max.: 0-1 VDC to 0-10 VDC
  • Bipolar voltage: ±1 VDC to ±10 VDC
  • Current: 0-2 mADC to 0-20 mADC, 20 V compliance, 1000 Ω at 20 mA

Milliamp output can be field wired for sink or source

Output Calibration Multi-turn zero and span potentiometers for each output channel±15% of span adjustment range typical
Output Loop Power Supply 20 VDC nominal, regulated, 25 mADC, <10 mVRMS max. ripple. May be selectively wired for sinking or sourcing mA output
Output Test Front button sets output to test level. Enabled via pushbutton.

  • Default setting approximately 50% of span
  • Potentiometer adjustable 0-100% of span
Output Ripple and Noise Less than ±0.2% of span
Linearity Better than ±0.25% of span
Ambient Temperature Range and Stability “10°C to +60°C operating ambientBetter than ±0.02% of span per °C stability
Response Time 50 milliseconds, nominal per channel used
Isolation 1200 VRMS minimum

  • Full isolation: power to each input, power to output, each input to output.
  • Non-isolated: input to input
Housing
  • IP 40, requires installation in panel or enclosure
  • For use in Pollution Degree 2 Environment
  • Mount vertically to a 35 mm DIN rail
Connectors Four 4-terminal removable connectors, 14 AWG max wire size
Power 9-30 VDC or 10-32 VAC 50/60 Hz, 4 W maximum